Cable HS XKDCu(Al)T 500 mm² Cu 60 kV

Description

Description

Standards

  • Test
    IEC 60840; IEC 62067
  • National
    HD 632 Section O

Applications

  • Underground distribution networks
  • Pipe laying and ground laying
  • Installation in electrical substations

These products are manufactured according to your specifications. Therefore, there is no standard product list. For more information, please contact us.

 

Construction

  • Copper or aluminum conductor
  • Extruded inner semi-conductor
  • Cross-linked PE insulation (XLPE)
  • Extruded outer semi-conductor
  • Semi-conductive swelling tape
  • Metal shielding
  • Semi-conductive swelling tape
  • Radial sealing (copper or aluminum tape)
  • Outer HDPE sheath

Properties

  • Longitudinal and radial sealing provided by two layers of tapes that swell in the presence of moisture and prevent the spread of water in case of injury to the sheath
  • Special abrasion resistant PE outer jacket with low shrinkage rate
  • Cross-linked PE insulation (XLPE) with high dielectric strength and low losses
  • Halogen free

Characteristics

Characteristics

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
500 mm²
Conductor diameter
26.5 mm
Diameter over insulation
48.9 mm
Outer Diameter
60.4 mm
Screen section
95 mm²
Approximate weight
7.5 kg/m

Electrical characteristics

Electrical characteristics

Operating voltage
60 kV
Permissible short circuit current screen 1s
15.0 kA
Permissible short circuit current conductor 1s
71 kA
Max. DC resistance of the conductor at 20°C
0.037 Ohm/km
Capacity core to screen
0.26 pF/m
I max. @ 90°C-buried in trefoil joined
800 A
I max. @ 90°C-buried in trefoil spaced
830 A
I max. @ 90°C-buried in flat formation joined
745 A
I max. @ 90°C-buried in flat formation spaced
825 A
I max. @ 75°C-buried in trefoil joined
720 A
I max. @ 75°C-buried in trefoil spaced
745 A
I max. @ 75°C-buried in flat formation joined
670 A
I max. @ 75°C-buried in flat formation spaced
740 A
Load factor
1
Sheaths grounding
1 point
Thermal soil resistivity dry zone
0.85 °K.m/W

Mechanical characteristics

Mechanical characteristics

Maximum tensile load during service (Tl)
3000.0 daN

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Ambient ground temperature
20 °C
Laying operation bending radius
2200 mm
Laying depth, center of system
1000 mm
Laying tube diameter
100 mm
Distance between tubes (X)
170 mm

Resources

Resources

Documentation

Construction pdf — 292.1 kB

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close